| Kernel driver g762 | 
 | ================== | 
 |  | 
 | The GMT G762 Fan Speed PWM Controller is connected directly to a fan | 
 | and performs closed-loop or open-loop control of the fan speed. Two | 
 | modes - PWM or DC - are supported by the device. | 
 |  | 
 | For additional information, a detailed datasheet is available at | 
 | http://natisbad.org/NAS/ref/GMT_EDS-762_763-080710-0.2.pdf. sysfs | 
 | bindings are described in Documentation/hwmon/sysfs-interface.rst. | 
 |  | 
 | The following entries are available to the user in a subdirectory of | 
 | /sys/bus/i2c/drivers/g762/ to control the operation of the device. | 
 | This can be done manually using the following entries but is usually | 
 | done via a userland daemon like fancontrol. | 
 |  | 
 | Note that those entries do not provide ways to setup the specific | 
 | hardware characteristics of the system (reference clock, pulses per | 
 | fan revolution, ...); Those can be modified via devicetree bindings | 
 | documented in Documentation/devicetree/bindings/hwmon/g762.txt or | 
 | using a specific platform_data structure in board initialization | 
 | file (see include/linux/platform_data/g762.h). | 
 |  | 
 |   fan1_target: | 
 | 	    set desired fan speed. This only makes sense in closed-loop | 
 | 	    fan speed control (i.e. when pwm1_enable is set to 2). | 
 |  | 
 |   fan1_input: | 
 | 	    provide current fan rotation value in RPM as reported by | 
 | 	    the fan to the device. | 
 |  | 
 |   fan1_div: | 
 | 	    fan clock divisor. Supported value are 1, 2, 4 and 8. | 
 |  | 
 |   fan1_pulses: | 
 | 	    number of pulses per fan revolution. Supported values | 
 | 	    are 2 and 4. | 
 |  | 
 |   fan1_fault: | 
 | 	    reports fan failure, i.e. no transition on fan gear pin for | 
 | 	    about 0.7s (if the fan is not voluntarily set off). | 
 |  | 
 |   fan1_alarm: | 
 | 	    in closed-loop control mode, if fan RPM value is 25% out | 
 | 	    of the programmed value for over 6 seconds 'fan1_alarm' is | 
 | 	    set to 1. | 
 |  | 
 |   pwm1_enable: | 
 | 	    set current fan speed control mode i.e. 1 for manual fan | 
 | 	    speed control (open-loop) via pwm1 described below, 2 for | 
 | 	    automatic fan speed control (closed-loop) via fan1_target | 
 | 	    above. | 
 |  | 
 |   pwm1_mode: | 
 | 	    set or get fan driving mode: 1 for PWM mode, 0 for DC mode. | 
 |  | 
 |   pwm1: | 
 | 	    get or set PWM fan control value in open-loop mode. This is an | 
 | 	    integer value between 0 and 255. 0 stops the fan, 255 makes | 
 | 	    it run at full speed. | 
 |  | 
 | Both in PWM mode ('pwm1_mode' set to 1) and DC mode ('pwm1_mode' set to 0), | 
 | when current fan speed control mode is open-loop ('pwm1_enable' set to 1), | 
 | the fan speed is programmed by setting a value between 0 and 255 via 'pwm1' | 
 | entry (0 stops the fan, 255 makes it run at full speed). In closed-loop mode | 
 | ('pwm1_enable' set to 2), the expected rotation speed in RPM can be passed to | 
 | the chip via 'fan1_target'. In closed-loop mode, the target speed is compared | 
 | with current speed (available via 'fan1_input') by the device and a feedback | 
 | is performed to match that target value. The fan speed value is computed | 
 | based on the parameters associated with the physical characteristics of the | 
 | system: a reference clock source frequency, a number of pulses per fan | 
 | revolution, etc. | 
 |  | 
 | Note that the driver will update its values at most once per second. |